General specifications
|
|
Signal type
|
Digital Input
|
|
Supply
|
|
Connection
|
Power Rail or terminals 14+, 15-
|
|
Rated voltage
|
19 ... 30 V DC
|
|
Ripple
|
≤ 10 %
|
|
Rated current
|
45 ... 70 mA
|
|
Power dissipation
|
1.2 W
|
|
Input
|
|
Connection side
|
field side
|
|
Connection
|
terminals 1-, 2+, 3-; 4-, 5+, 6-
|
|
Rated values
|
acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
|
|
Open circuit voltage/short-circuit current
|
approx. 8 V DC / approx. 8 mA
|
|
Switching point/switching hysteresis
|
1.2 ... 2.1 mA / approx. 0.2 mA
|
|
Pulse/Pause ratio
|
min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation)
|
|
Line fault detection
|
breakage I ≤ 0.15 mA , short-circuit I > 6 mA
|
|
Output
|
|
Connection side
|
control side
|
|
Connection
|
output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
|
|
Output I ... IV
|
Signal I ... Signal IV ; relay
|
|
Contact loading
|
253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
|
|
Energized/De-energized delay
|
approx. 30 ms / approx. 30 ms
|
|
Mechanical life
|
5 x 106 switching cycles
|
|
Collective error message
|
Power Rail
|
|
Transfer characteristics
|
|
Switching frequency
|
≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation)
|
|
Galvanic isolation
|
|
Input/Output
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
|
Input/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
|
Output/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
|
Output/Output
|
basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
|
Indicators/settings
|
|
Display elements
|
LEDs
|
|
Control elements
|
DIP-switch
|
|
Configuration
|
via DIP switches
|
|
Labeling
|
space for labeling at the front
|
|
Directive conbity
|
|
Electromagnetic compatibility
|
|
|
|
Directive 2014/30/EU
|
EN 61326-1:2013 (industrial bs)
|
|
Low voltage
|
|
|
|
Directive 2014/35/EU
|
EN 61010-1:2010
|
|
Conbity
|
|
Electromagnetic compatibility
|
NE 21:2006
|
|
Degree of protection
|
IEC 60529:2001
|
|
Input
|
EN 60947-5-6:2000
|
|
Ambient conditions
|
|
Ambient temperature
|
-20 ... 60 °C (-4 ... 140 °F)
|
|
Mechanical specifications
|
|
Degree of protection
|
IP20
|
|
Connection
|
screw terminals
|
|
Mass
|
approx. 150 g
|
|
Dimensions
|
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
|
|
Mounting
|
on 35 mm DIN mounting rail acc. to EN 60715:2001
|
|
Data for application in connection with hazardous areas
|
|
EU-type examination certificate
|
ZELM 99 ATEX 0009
|
|
|
Marking
|
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
|
|
|
Input
|
Ex ia IIC
|
|
|
Voltage
|
10 V
|
|
|
Current
|
14 mA
|
|
|
Power
|
35 mW (linear characteristic)
|
|
Supply
|
|
|
|
Maximum safe voltage
|
40 V DC (Attention! Um is no rated voltage.)
|
|
Output
|
|
|
|
Contact loading
|
230 V AC + 10 % / 2 A / 100 VA / cos φ ≥ 0.7; 40 V DC / 2 A resistive load
|
|
Fault indication output
|
|
|
|
Maximum safe voltage
|
40 V DC
|
|
Galvanic isolation
|
|
|
|
Input/b
|
not available
|
|
|
Input/Output
|
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
|
|
|
Input/power supply
|
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
|
|
Directive conbity
|
|
|
|
Directive 2014/34/EU
|
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000
|
|
International approvals
|
|
UL approval
|
|
|
|
Control drawing
|
116-0145
|
|
IECEx approval
|
|
|
|
IECEx certificate
|
IECEx TUN 04.0003
|
|
|
IECEx marking
|
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
|
|
General inbation
|
|
Supplementary inbation
|
Observe the certificates, declarations of conbity, instruction manuals, and manuals where applicable. For inbation see www.pepperl-fuchs.com.
|